Honeywell C7232A1024 Carbon Dioxide Sensor
The Carbon Dioxide (CO2) Sensors and Controllers are stand-alone carbon dioxide (CO2) sensors for use in determining ventilation necessity with HVAC controllers. The sensor measures the CO2 concentration in the ventilated space or duct. The sensors are used in ventilation and air conditioning systems to control the amount of fresh outdoor air supplied to maintain acceptable levels of CO2 in the space.
SPECIFICATIONS:
Description Carbon Dioxide Sensor, Non-dispersive Infrared (NDIR), Wall Mount, LCD Display
Mounting Wall mount
Display Yes
Carbon Dioxide Range 0 to 2000 ppm, adjustable
Analog Current Output 0/2 - 10 Vdc or 0/4 - 20 mA selectable, w/ one relay output
Relay Output One: Normally Open SPST
Electrical Connections Six leadwires, 20-gauge, 8 in. long
Voltage 24 Vac/dc ±20%,
Frequency 60 Hz
Frequency 50 Hz
Operating Temperature Range (F) 32 F to 122 F
Operating Temperature Range (C) 0 C to 50 C
Timing (response) 1 minute
Sensor Type Non-dispersive Infrared (NDIR)
Accuracy 5% full scale
Dimensions (in.) 5 1/16 in. high x 3 5/32 in. wide x 2 in. deep
Dimensions (mm) 128 mm high x 80 mm wide x 25 mm deep
Includes No Honeywell Logo
Contact Ratings 1 A @ 50 Vac/24 Vdc